MAX15303 PMBus Command Set User’s Guide
Page 28 of 52
STATUS_INPUT
Reference:
Standard Command
Lockable:
N/A
Command Code:
0x7C
Format:
Bit field
Data Bytes:
1
Units:
N/A
Transfer:
Read Byte
Factory Value:
N/A
Description/Notes:
See Section 17.5 of the PMBus Specification Part II.
Bits #6, #5, #2, #1, and #0 are not implemented in the MAX15303 because the corresponding fault
commands are not supported.
STATUS_TEMPERATURE
Reference:
Standard Command
Lockable:
N/A
Command Code:
0x7D
Format:
Bit field
Data Bytes:
1
Units:
N/A
Transfer:
Read Byte
Factory Value:
N/A
Description/Notes:
See Section 17.6 of the PMBus Specification Part II.
Bits #5 and #4 are not implemented in the MAX15303 because the corresponding fault commands
are not supported.
STATUS_CML
Reference:
Standard Command
Lockable:
N/A
Command Code:
0x7E
Format:
Bit field
Data Bytes:
1
Units:
N/A
Transfer:
Read Byte
Factory Value:
N/A
Description/Notes:
See Section 17.7 of the PMBus Specification Part II.